Start with the operator’s decision

A useful FM request describes a decision: identify equipment, order a part, access maintenance or plan replacement. Then define assets, necessary information, milestone and producer responsibility. Manufacturer and model reference help select a part; serial and location distinguish the instance. Collection should remain proportionate. Requesting every property for every object guarantees neither reliable information nor practical use. Each requested field should have an identified operational purpose.

Write mappings that preserve meaning

For each target field, record IFC path, type or occurrence origin, value type, unit, transformation and missing-value rule. Choose a matching key and check duplicates across the complete register. A paginated interface is not the audit population. Systems, locations and documents become target relationships; flattened text can lose their identity. Preserve source values when business normalisation is applied, so the transformation remains explainable and reversible.

Check documents and maintenance

A manual link must be accessible and relevant to the delivered model, variant and revision. Check status, language, owner and asset relation. Distinguish warranty, service life and maintenance interval; fifteen-year service life does not mean maintenance every fifteen years. A task needs frequency, trigger, source and responsibility. Safety and access information requires review appropriate to the intervention, not merely presence in a Pset.

Accept the result in the target

Verify handover through trial import, target re-read and update testing. Two unchanged reimported assets should remain two under agreed rules. Inspect keys, values, relationships, attachments, exclusions and outstanding issues. COBie has structure, process, version and profile; 2.4 Floor vocabulary cannot be transferred unchecked to V3 Level. A generic CSV may be useful without being a validated COBie delivery. Assign responsibility for accepting results and updating them later.

Worked example

For the Duplex door, a reliable mapping retains attr.GlobalId, OverallWidth=1.25 m and Thickness occurrence origin through #38574. Unknown information stays unknown. Filling a table does not replace checking those values in the target CMMS.

  1. Operational decision
  2. Information requirement
  3. IFC → mapping → CMMS
  4. Trial import + update

Questions and answers

The facility manager needs the correct spare part. Which pair is directly useful?

Verified manufacturer and model reference linked to the instance. Start with the decision to identify needed information. Also check variant, compatibility and applicable manual; similar references do not guarantee the right part.

After correction, a second CMMS import runs. Which verification closes the test?

Re-read target values, identities, relationships, duplicates and history Transfer success does not prove the business result. Handover evidence connects source, transformation and actual target state.

Put it into practice

Review cards and solve cases

Start free training →Worked example IFC →

Official sources

Content references: 30 October 2026. Consult the sources to verify their version and applicability.

Published by BIMCheck Consulting · Publisher: Winter Fernandes

Content references: 30 October 2026. Consult the sources to verify their version and applicability.

Independent, non-certifying training. Check the IFC schema, standards edition and project-specific requirements.

About and editorial method